Earthing Switch MJW-126

  • Share:

Description

 

MJW-126 is a earthing switch for an open installation. The Earthing switch is intended for safe grounding of equipment during repair and maintenance, is a high-voltage device for outdoor installation of a three-phase AC network with a rated voltage of 110-220 kV and a frequency of 50 Hz, used to ground current conductors disconnected from power supplies. The earthing switch complies with the requirements of IEC 62271-102.

 

Rated voltage, kV: 110, 220

Maximum working voltage, kV: 126, 252

MJW-126, 252 is used to safely ground electrical equipment during repairs and maintenance.

Parameters

 

Operating Conditions of MJW-126 and MJW-252

  1. Altitude: up to 2000 m.
  2. Ambient temperature: from -45°C to + 45°C.
  3. Humidity: the average value of relative humidity during the day is not more than 95%; the average value of relative humidity during the month is not more than 90%.
  4. Seismic resistance up to 8 points.
  5. Environment is not explosive, does not contain dust, aggressive gases and vapors in concentrations that destroy metal and insulation.
  6. Lifetime — 30 years.
  7. Warranty period from the date of commissioning — 2 years.

 

Parameters of MJW-126 and MJW-252

Parameter Unit. Data
Rated voltage kV 110 220
Highest operating voltage kV 126 252
Rated peak withstand current A 80,100 100,125
Rated thermal current for 3 s: kA 31.5,40 40,50
Power frequency rated withstand voltage 230 460
kV kV 265 530
Lightning impulse withstand voltage 550 1050
kV kV 630 1200

 


Parameter
Unit Data
Creepage distance II mm 20 20
III mm 25 25
IV mm 31 31
Current breaking capacity (induced current) Electro

magnetic connection

A А 50 80
kV kV 0.5 1.4
Electro static connection A А 1.25
kV kV 3 5
Mechanical resource Number of cycles 3000 3000
Minimum breaking load N 4000,6000,8000 8000^Н
Weight of one pole Kg 110 230
Exposure to radio waves μV <2000 <2000

 

Solutions

 

Dimensions of MJW-126 and MJW-252

MJW-126-2

 

MJW-126-3

 

Appearance and dimensions of the grounding conductor MJW-126

Note 1: the drawing shows one phase. In the full drawing, the angle between the lever and the axial line of the porcelain insulator is 45 °, the rest is similar. Note 2: the distance between the poles is not less than 1500 mm.

MJW-126-4

 

Appearance and dimensions of the earthing switch MJW252-252

Note 1: the drawing shows one phase. In the full drawing, the angle between the lever and the axial line of the porcelain insulator is 45 °, the rest is similar. Note 2: the distance between the poles is not less than 3000 mm.

MJW-126-5