Models MGW1-12, 24, 40.5  are outdoor disconnectors, designed to turn on and off de-energized sections of the electrical circuit with a rated voltage of 10 kV, 20 kV or 35 kV and an alternating current frequency of 50 and 60 Hz. The special version can be used in severe pollution areas.

 

Environmental conditions

Height: <3000m;

Ambient temperature: -30 ° С- + 40 ° С;

Wind speed: <35 m / s;

Air pollution: IV;

Earthquake intensity: <8 degrees;

Ice thickness: <10 mm.

Disconnector MGW1-12-2

Parameters

 

Technical Specifications for MGW1-12 Disconnector:

№.ElementUnitData
1Rated voltage, kVkV10, 20, 35
2Maximum operating voltagekV12, 24, 40.5
3Rated currentA630, 1000, 1250
4Rated industrial frequencyHz50/60
5Rated peak withstand currentkA50, 63
6Rated short-time withstand currentkA20, 25
7Rated short-time withstand currents4
8Main circuit resistanceμOhm12kV=S8024kV=S9040.5kVs=100
91 minute (dry) withstand voltage of industrial frequencykV42/4850/6095/115
101 minute (wet) withstand voltage of industrial frequency345085
11lightning impulse withstand voltage (peak)75/85125/145185/215
12Switching cyclescycle2000

 

Solutions

 

The primary function of a disconnector is to serve as a visual indicator of whether an electrical connection is open or closed; this lets network operators know if the circuit/equipment is either energised or de-energised.

It is important operators can confirm the energised state of the circuit/equipment in order that they can safely perform inspections, maintenance, and repairs, without unnecessary risk.

 

Dimensions of MGW1 Disconnectors (mm)

МодельDimensions (mm)
BCDEF
MGW1-12/630-2040010001200565510
MGW1-24/630-203753951155695650
MGW1-40.5/630-2050012501450815728

 

Disconnector MGW1-12-3

Vertical (V)130 °
Horizontal (H)50 °
Mounting MethodA

 

Appearance and dimensions of the disconnector MGW1

МодельABCDE
MGW1-12D/12504001050400590403
MGW1-24D/12504501160450650530
MGW1-40.5D/12505001300550730620

 

Models with grounding knives

Disconnector MGW1-12-5

Models with grounding knives and lightning arrestor

  1. The housing of the insulating base
  2. Support insulator
  3. Traction insulator
  4. Contacts
  5. Spring
  6. Lightning arrestor
  7. Shaft crank
  8. Contact knife
  9. Grounding knife.

Hot Tags: MGW1 disconnector, China, OEM supplier, manufacturers, factory, wholesale, disconnecting switch, switch disconnector, automation, grounding, retrofit