Load Switch MFZW32-40.5

  • Share:

Description

 

The load switch MFZW32-40.5 is a three-phase load switch of an outdoor installation (open installation) of 35 kV that provides switching on and off under load (without damage) sections of a three-phase alternating current circuit, with earthed or isolated neutral in emergency conditions.

Rated current, A — 630, 1250

Rated voltage, kV — 35

The maximum operating voltage, kV — 40.5

Rated frequency, Hz — 50

Parameters

 

Main Technical Parameter MFZW32-40.5:

NoNameUnitValue
1Rated voltageKV40.5
2Rated currentA630
3Rated frequencyHz50
4Rated peak withstand currentKA50
5Rated short time withstand currentKA20
6Rated short time withstand current durations4
7Rated active load breaking currentA630
8Rated closed loop breaking currentA630
9Rated cable charging breaking currentA10
105% rated active load breWng currentA31. 5
11Rated breaking capacLy of no-load transformerKVA1250
12Rated short circuit closing currentKA50
13Major loop resistance卩Q<95
141min power frequency withstand voltage(RMS)Dry testPole-to-pole, pole-to earthKV95
Isolating fracture115
Wet testPole-to-pole, pole-to earth85
15Lightning impulse withstandvoltage (peak)Pole-to-pole, pole-to earthKV185
Isolating fracture215
16Mechanical lifeTimes10000

 

NoNameUnitValue
17Three-phase opening/closing asynchronismms<15
18Motor voltage and powerV W£220 <200
19Contact knife breaking position deviationmm<5
20Main contact knife pressureN420±42
21Clearance between contact knivesmm>360
22Rated peak operating torqueNm<300

 

Operating Conditions of MFZW32-40.5

  1. Altitude: up to 1000 m.
  2. Ambient temperature: from -35°C to + 45°C.
  3. Environmental Humidity: the average value of relative humidity during the day is not more than 95%;
  4. Seismic resistance up to 8 points.
  5. Do not operate in places where the circuit breaker may be exposed to flammable gas, where there is a danger of explosion, the risk of chemical corrosion, and where the equipment is subject to strong vibration.
  6. Estimated service life — 20 years
  7. Warranty Period — 12 months

 

Solutions

 

This load switch is composed of isolating switch, vacuum interrupter and operating mechanism and other parts. By using the principle of vacuum interrupter, with strong arcing ability, reliable performance, long service life, small volume, no explosion danger, no pollution. The product can be used in transmission and distribution system of electric power, metallurgy, mine, chemical industry and other departments as control equipment, especially suitable for frequent operation place.

MFZW32-40.5 -1

Hot Tags: MFZW32 Load Switch, China, OEM supplier, manufacturers, factory, wholesale, load break switch, SF6 switch, automation, mechanism, retrofit, switchgear