Description
Air insulated switchgear (AIS) series KYN28A-12 (GZS1) is armored removable AC metal- enclosed switchgear. It is suitable for three-phase AC 50Hz power system for receiving and distributing power and controlling, protecting and monitoring of the circuit in real time. The newly introduced and developed large current and high breaking switchgear can also be used as a high-voltage generator export.
Product reference standards:
GB1984 exchange high voltage circuit breaker,
GB3906 3 ~ 35 kV ac metal-enclosed switchgear,
GB/T11022 voltage switch equipment and control equipment standard public technical requirements,
DL/T404 indoor exchange high-voltage switchgear order technical conditions.
Operation conditions:
Normal operating conditions, according to the IEC International Standards listed below, for indoor switchgear.
Ambient air temperature
- Less than or equal to 40°C
- Less than or equal to 35°C on average over 24 hours
- Greater than or equal to -5°C (-25°C on request)
Altitude
- Less than or equal to 1000 m;
- Above 1000 m, a derating coefficient is applied (please consult us)
Atmosphere
- No dust, smoke, or corrosive or inflammable gas and vapor, or salt
- Earthquake intensity: Magnitude 8
Humidity
- Average relative humidity over a 24-hour period ≤ 95%
- Average relative humidity over a 1-month period ≤ 90%
- Average vapor pressure over a 24-hour period ≤ 2.2 kPa
- Average vapor pressure over a 1-month period ≤ 1.8 kPa