Description
The MFN5-12 load switch is a three-phase load switch for indoor installation, which enables switching on and off under load (without damage) sections of a three-phase alternating current circuit with earthed or isolated neutral during emergency conditions.
Rated current, A — 400, 630
Rated voltage, kV — 10
The maximum operating voltage, kV — 12.7
Rated frequency, Hz — 50
Rated short-time withstand current, kA / s — 12.5 / 4 20/2
Rated peak withstand current, kA — 31.5 / 50
Impulse voltage (peak) / ground, kV — 75/85
An SF6 load switch, or load break switch (LBS), utilizes sulfur hexafluoride (SF6) gas as an insulating and arc-quenching medium. Being colorless, odorless, and non-toxic, SF6 offers outstanding dielectric strength, making it a popular choice for high-voltage switching applications.