Vacuum Circuit Breakers MVS3-12 (ZN63M)

  • Share:

Description

 

The operation of closing the circuit breaker MVS3-12 (ZN63M) is carried out due to the traction force of the closing spring. The circuit breaker is tripped (including automatic shutdown at short-circuit currents or overloads) due to the energy stored by the circuit breaker springs when turned on. Arc extinction in the circuit breaker is carried out by vacuum interrupter chambers (VI).

The electric arc, due to the special shape of the contacts creating their own longitudinal (axial) magnetic field with a diffuse form of arc burning, decays and is extinguished. Due to the high dielectric strength of the vacuum gap, fractions of microseconds between contacts restore voltage.

The circuit breaker consists of three poles fixed to the circuit breaker housing. All body parts of the high-voltage part of the circuit breaker are made of insulating material, which allows it to be embedded in cells with limited space of the high-voltage compartment. Each pole contains a vacuum arrester, a mechanism for additional preloading of the VI contacts and current outputs.

The circuit breaker MVS3-12 (ZN63M) is equipped with a spring drive with low current consumption. A spring-loaded drive consists of an electric motor for charging a spring, a switching spring, an switching magnet, a block of mechanical latches, a damping hydraulic device, and a breaking electromagnet. The electrical circuit of the power supply and control circuit breaker is assembled on a panel mounted in the drive housing.

METTZ Group offer to our customers more than 50 modifications and types of VCB design.

Parameters

 

Main Technical Data

Rated voltage6-10 kV
Maximum working voltage12 kV
Rated currentOptions ranging from 630A to 4000A
Dielectric strength42 kV at 50 Hz industrial frequency
Test voltage of full lightning discharge75 kV
Symmetrical short-circuit breaking current16,20,25,31.5,40,50 kA
Nominal peak value of permissible through current40,50,63,80,100,125 kA
Thermal resistance current (4s)16,20,25,31.5,40,50 kA
Rated switching cycle0-0.3s-v0-180s-v0
Mechanical cycle life10,000
Switching TimesClosing <70ms, Opening <45ms, Off time <60ms
Power of the inclusion coil250 VA
Trip coil power250 VA

 

Vacuum circuit breakers MVS3-12 (ZN63M) are designed for operation in three-phase alternating current networks with a frequency of 50 Hz and a rated voltage of 6-10 kV with isolated or compensated neutral in normal or emergency conditions.

They can be used both in new construction and when replacing circuit breakers of previous years of manufacture. They can be installed in the design of existing cells and can be used in the development of new products.

 

Usage and Environmental Conditions

AltitudeUp to 1000 m
Temperature-25 °C to + 40 °C
HumidityDay and monthly averages of 95% and 90% respectively
Seismic resistanceUp to 8 points
EnvironmentNon-explosive, free from aggressive gases, vapors, or dust
Reliability RequirementsVarious mechanical and switching resistance cycles
Warranty2 years from commissioning
Lifespan25 years
Warranty period from the date of commissioning:5 years
The service life of circuit breakers to an average repair of:at least 12 years